COS-16 Pressure Reducing Valve


cos16 picture

(Patented)

COS-16 Specifications

ConnectionScrewed / Flanged
Body MaterialCast Iron
Operating Primary Pressure30-250 psig
0.2-1.6 MPaG
2-16 kg/cm²G
Pressure Adjustment Range 5-210 psig / 0.03-1.34 MPaG / 0.3-13.4 kg/cm²G
(must be within 10-84% of primary pressure;
and allowable differential pressure must be within 10-120 psi / 0.07-0.85 MPa / 0.7-8.5 kg/cm²)
Minimum Adjustable Flow Rate5% of rated flow rate
(2 1/2 - 4 inch / 65-100 mm : 10%)
Accuracy of Regulation+/- 1 psi / 0.01 MPa / 0.1 kg/cm²
(under steady flow conditions)
Maximum Operating Temperature428°F / 220°C
Seat Leakage Rating Less than 0.1% of rated flow rate
NOTE: Specifications vary according to country and standards; please contact KTE for more details.






NOTE: Specifications vary according to country and standards; please contact KTE for more details.
Specifications subject to change without notice.

Capacity Charts
Available upon request. Please contact TLV.


HOME | TLV | VALQUA | TSUBAKI | OKM | VENN | TOYO | ABOUT US | NEWS